Lesson 2.2 — Tools, Cables & Connectors

Competency 2 covers the toolkit: MC4 crimping tool (never pliers — a bad crimp is a future arc), DC-rated breakers and fuses, solar cable (UV-resistant, double-insulated, 4 or 6 mm²), battery lugs with heat-shrink, and cable ties rated for sun. Voltage drop discipline: keep DC runs short and fat — a 3% drop at 12 V is only 0.36 V, so panel-to-controller and controller-to-battery runs use generous cable and tight terminations.

  1. Strip solar cable to 8 mm
  2. Insert into MC4 pin, crimp with the rated tool
  3. Tug-test, then click into housing
  4. Verify polarity with meter before connecting
  5. Label + and − at both ends
SEAL — South East Asia Learning Identifier & Skills Portal · Prepared for MLVT Executive approval and TVET institute review · Derived from the Australian National Training Register (training.gov.au, CC-BY) and aligned to the Cambodian Qualifications Framework and DSC Standard Training Packages · Delivered via Gibble SMS · July 2026